Energy Storage System

Liquid cooled energy storage system ST13760kWh(DCDC American type transformer )

   Battery cabinet data

       ·ST13760kWh-3150kW-MV-4h   ST13760kWh-3450kW-MV-4h

  · (cell type):3.2 V / 280 Ah

  · (System battery configuration ):384S10P * 4

  · Nominal Battery capacity:3440 kWh * 4

  · Battery voltage range:1036.8 V - 1401.6 V

  · (BMS Communication interfaces ):Ethernet

  · (BMS Communication protocols ):Modbus TCP


  AT AC DATA


ST13760kWh-3150kW-MV-4hST13760kWh-3450kW-MV-4h
Nominal power at AC3150 kVA3450 kVA
AC Current Distortion rat< 3 % (at nominal power)< 3 % (at nominal power)
DC component< 0.5 %< 0.5 %
Nominal voltage at AC630 V690 V
Nominal grid voltage range535.5 V - 693 V586.5 V - 759 V
Power factor at nominal power> 0.99 (at nominal power)> 0.99 (at nominal power)
Adjustable reactive power range- 105 % - 105 %- 105 % - 105 %
Nominal grid frequency50 Hz50 Hz
Grid frequency range45 Hz - 55 Hz45 Hz - 55 Hz
Isolation mode                               Isolation Transformer

          


  Transformer data


ST13760kWh-3150kVAST13760kWh-3450kVA
Transformer rated power3150 kVA3450 kVA
LV / MV voltage0.63 kV / 37 kV
Section                                            Dy11

  


  system data

 


ST13760kWh-3150kVAST13760kWh-3450kVA
Dimensions of battery system(WHD)                 9340 mm * 3150 mm * 1730 mm
Weight of battery                                 ≤ 33.5 t

Dimensions of Converter voltage 

rise cabinet(WHD)

                6140 mm * 2515 mm * 2515 mm

Weight of Converter voltage rise

system

                                  14 t

Degree of protection(Converter

voltage rise system)

                                  IP54
Degree of protection(battery room)                                  IP55
Operating temperature range                 - 35 ℃ - 50 ℃ ( > 45 ℃derating )
Relative humidity range                    0 % - 95 % (non-condensing)
Battery cabinet cooling mode                           Liquid cooling
Current converter colling modeTemperature controlled forced air cooling
Fire safety equipment(battery room)

FM200 gas fire,flammable gas detector and exhausting

system,water fire

Communication interfaces                                Ethernet
External Communication protocols                Modbus TCP;IEC61850(optional)
 Max. working altitude                                 5000M